SD-8
Specifications for Automatic Telephone Dialing System
The automatic
telephone dialing system as described here shall function as
specified without exception.
- The
entire system shall be manufactured by one company and
covered by one warranty. The entire system shall be solid
state electronics.
- All
alarm contact connections to the main board shall be thru
a screw lug type connector. This connector shall be a
modular one piece electronic cage-clamp design to
accommodate #14 to #30 AWG wire. The system shall
incorporate light emitting diodes and opto isolators
which shall sense the alarm condition and shall provide
no direct electrical connection between the outside alarm
contacts and the main board.
- The
system shall be housed in a glass filled Polycarbonate
enclosure with a clear Polycarbonate window fitted with
an oil resistant gasket.
- The
alarm notification system shall be as manufactured by H
& R ELECTRONICS, INC. DANIELSVILLE, GA 706.789.2915
or 800.550.0774 and shall be equal in quality and
performance to the model SD-8 as manufactured by
H & R ELECTRONICS, INC.
- The
alarm notification message and systems prompts shall be
voice digitized and stored on memory chips. The quality
of the voice reproduction must be equal to telephone
conversation and must be capable of carrying the tone and
inflection of the voice message. The voice messages and
prompts must be capable of being sustained in the absence
of all electrical power for a time period greater than 10
years.
- The
voice messages and prompts shall be capable of being
installed either at the factory, in the field at the
location, 100 feet from the physical location of the
system, or from another telephone via telephone network
(SOUTHERN BELL TELEPHONE, MOUNTAIN BELL TELEPHONE, etc.).
- The
system shall provide a means of remotely programming the
voice prompts on the system at the transmitter site. This
will require that the programming device shall come
equipped with a provision which will allow the
programming personnel the ability to record the message
at a distance of 100 feet from the main system on
location. The purpose of this feature is to allow the
programming of the voice messages on site should the
noise level at the specific location of the system be
such that the background noise would be unacceptable.
This provision is in addition to the remote programming
feature.
- In
addition the system must be capable of removing the
entire speaker and keypad assembly to prevent any
unauthorized operation of the system.
- The
system must be capable of an unlimited vocabulary and not
limited to a list of specific words or phrases. The
telephone numbers on the system shall be stored on data
chips which have a data retention of a least 100 years
per the manufacturer data sheets. This will prevent the
loss of telephone numbers in the event of a total
collapse of all power.
- A total
speech time of 3 minutes shall be considered standard.
Total speech times of less than 3 minutes will be
unacceptable. The speech time shall adequate to define
the nature of the alarm and the required response for
each of the 8 alarm conditions. The time allowed for this
description shall be a minimum of 10 seconds of voice
description per each alarm condition. Every alarm
condition monitored shall have a minimum of 10 seconds of
voice message to describe the alarm condition in addition
to other speech requirements listed in this
specification. The length of each message is independent
and can be as short or as long as required during the
total time of 90 seconds for all alarm messages. The
system shall come with a built-in speaker which will
allow the personnel at the site to monitor the outgoing
messages. The remote speaker shall have the provision to
be remotely mounted from the main system to another
location up to 50 feet from the main system without
additional components or cards.
- The
audio system shall be capable of running a multi-speaker
system with an adjustable volume output available to
compensate for the number and quality of speakers
installed. Speakers are optional and are defined
elsewhere in the specifications.
- The
system shall have the ability to delay the call-out of an
active alarm based on a time delay selected by the
customer. The time delay shall range from 00 seconds
(immediate) to 2.5 hours. This time is selected by the
customer and may be adjusted on site or remotely. Each
individual alarm contact shall have it's own separate,
independent and adjustable time delay. When the time
delay has expired for any channel the system will call
out and deliver a voice message. The voice message which
is delivered upon the time out of an alarm condition
shall advise the called party the location of the station
calling, the nature of the problem, the alarms that are
active and the required response and instructions for
acknowledging the call.
- The
system shall accommodate either N/O or N/C dry contacts
as selected by the customer. This selection shall be made
either at the system, or up to 100 feet from the system,
or remotely via touch-tone telephone.
- The
system shall incorporate a fail-safe time delay which
will provide the acknowledging party a preset time to
arrive at the station to reset the system. Should the
party fail to get to the site or fail to call and buy
more time on the failsafe timer, if in alarm, then the
system will automatically begin the dialing sequence
again. New alarms during the fail-safe time will not
cause the system to dial out until the time delay has
expired. The system shall offer the opportunity to each
called person via the telephone to send an acknowledgment
signal to the dialer. The called party communicates via a
touch-tone telephone with the system. Entering the proper
acknowledge code will cause the system to set the
fail-safe timer. When the system receives a proper
acknowledgment tone then the system shall provide a
positive announcement to the called party confirming the
receipt of the acknowledgment tones. This shall be in the
form or a statement which says "ACKNOWLEDGMENT
RECOGNIZED" or any other statement which the
customer may chose to announce.
- The
reset switch feature of the system shall normally be
located on the outside of the enclosure. The reset switch
shall also be capable of being mounted up to 100 feet
from the outside of the location of the system. The reset
switch shall reset the customer preselected values into
the system.
- In
addition the alarm notification system shall provide
voice prompts to aid the customer in installing database
information that will include the alarm messages, the
telephone numbers and other operations required under
this section.
- The
system shall be capable of monitoring a minimum of eight
different alarm conditions as a standard feature without
modification or additional board requirements. The system
shall be capable of delivering multiple fault messages in
the event that multiple alarms are tripped and timed out.
In addition to these eight conditions, the system shall
be capable of internally monitoring the presence of A/C
power. Should the customer elect to utilize the A/C power
fail the customer selects a time period which is the
delay before calling. Should the A/C power be removed
from the system and the time delay is decremented to
zero, the system shall initiate a structured dial out
procedure and deliver the power fail message in addition
to any other alarm which is timed out and tripped.
- In
addition to being capable of dialing eight different
telephone numbers, the system shall be capable of dialing
any ascending customer programmable sequence of one to
eight telephone numbers. This shall allow the temporary
removal of one or more telephone numbers without removing
the actual telephone number(s) from the directory. Thus a
temporary removal or installation of one or more
telephone numbers is accomplished in one process which
selects the telephone sequence to be dialed.
- The
system shall provide a minimum of one telephone sequence
for dial out. The customer shall have the ability to
program any desired telephone dialing sequence into the
system, at the location of the system, remotely up to 100
feet from the system, or by way of telephone connection.
The system shall be capable of programming delays within
a telephone number and shall be capable of dialing up to
16 digits for each of the programmed telephone numbers.
When programming locally each telephone number shall be
displayed on a LCD prior to being entered into the
system. All tools and devices required to program or
change any data in the system shall be furnished by the
manufacturer.
- The
customer shall be trained in the operation of the system
by factory authorized personnel to insure that at least
one employee of the customer is fully trained on the
operation of the system.
- The
system shall have, in addition to a voice message, a
visual indicator system. This system shall be composed of
various LED's. The color and location of the LED's shall
be such that a trained operator shall be able to make a
determination from across the room as to the status of
the system. The system shall provide eight red LED's that
shall describe which channels being monitored that are in
alarm. Also required is a set of eight red LED's that
shall define the status of the contacts whether normally
open or normally closed. A third set of eight green LED's
for each channel shall be provided which will define
which channel(s) is (are) bypassed. Each channel shall be
equipped with a separate switch that can individually
bypass the selected channel during the time where the
reporting of the channel would constitute a nuisance
alarm. This switch is customer accessible and provides a
means of temporarily bypassing any or all alarms as may
be required by the customer.
- The
system shall be capable of establishing an on/off of the
alarm monitoring. This feature is selected by the
customer. The status of the ON or OFF alarm monitoring
shall be displayed by a LED.
- The
system shall have an indicator light that will confirm
that the system has terminated the dialing sequence
properly. Also the system shall have an indicator LED
that will define when the system has been acknowledged
and is waiting in the fail safe mode for a local reset or
fail-safe timeout.
- The
system shall have a minimum of 36 LED's; or if a lesser
number, shall incorporate a 6-line 20 character LCD.
- The
system shall be under the control of a microprocessor
that shall control the activities of the system. The
microprocessor and all major and minor integrated circuit
devices shall be installed into gold plated plug in
sockets for ease of change out during the coming years.
- The
potential for hostile environmental condition could
possibly affect the performance of the system. As a
precautionary measure the temperature range of the
microprocessor used in this application shall be
guaranteed to perform from -40 degrees to + 100 degrees
C. These are the absolute minimum and maximum temperature
acceptable gradients. Lesser quality microprocessors will
not be considered acceptable for the intended use as
described herein.
- To
provide for rapid diagnostic evaluation as to the system
ability to perform, the system shall have indicator
lights that will define the existence of each of the
major and minor voltages present on the board such that
an experienced operator would be able quickly to look and
determine the operational status of the system via the
indicator lights. A minimum of three indicator lights to
adequately define all system voltages shall be required.
In addition a LED shall be present for the system status,
either on or off. Also the 8 LED's which monitor the
operational characteristics of the microprocessor shall
be provided.
- The
entire system shall be designed to operate in the absence
of A/C power via the use of the stand-by batteries that
shall sustain the operation of the system in a power
failure condition. The batteries shall be maintained in
peak performance by a controlled onboard recharging
circuit. Backup batteries shall provide power to the
system in the absence of A/C line voltage and shall
switch automatically as required to provide uninterrupted
service. The battery standby time shall be 12 hours
without A/C service. The voice messages and data stored
shall not require any power to maintain the integrity of
the data. The entire assembly shall not have any internal
or exposed A/C lines that would be capable of inflecting
a shock to maintenance personnel. All incoming A/C or D/C
service shall be low voltage (12 volts or less).
- The
system shall be capable of dialing out on the standard
telephone network or on cellular telephone lines and
shall not require dedicated lines. The system must
incorporate the ability to recognize an incoming call, a
busy signal, and recognize touch-tone input signals. In
addition to dialing telephone numbers designed to ring
telephones at an office or home location, the system
shall be capable of dialing a pager and delivering a
voice or digital message.
- The
standard system shall contain without modification the
ability to dial a digital pager and deliver a signal that
will translate on the pager LCD display a minimum of a
3-digit identification (location) code and a dash, then
the numerical digit that corresponds to the alarm
condition(s) that are active at the time of the call. The
system shall also be normally capable of identifying the
alarm condition of A/C power fail should this alarm be
selected and timed out. Systems which provide only the
telephone number on a pager shall be considered
unacceptable for the intended use described herein.
- The
system shall be capable of recognizing when the dialed
number is taken off- hook (answered). The system shall be
capable of recognizing a busy signal. Should a busy
signal be encountered, the system shall immediately
discontinue this dialing cycle and begin dialing the next
telephone number in the sequence. The system shall be
capable of allowing the end user the ability to establish
the number of rings of the telephone prior to hang up.
The customer may select from 1 ring to 99 rings. The
number of rings shall be capable of being changed
remotely.
- The
system shall incorporate an access protection system that
would make access to the system difficult to uninformed
individuals. The minimum level of protection for
accessing the system shall be a three digit entry, plus a
four-digit security code. The access to the Main Menu
shall be protected by a 4 digit access code that is under
the control of the customer and can be changed by the
customer to suit their specific requirements. Remote
access to the system shall be allowed only under the
proper code entry that require a minimum of 7 correct
entries prior to access to the Main Menu.
- Remote
access shall be provided to obtain a current status of
the system that will identify the location of the station
by voice description and then describe any alarms that
are active. Should no alarms be active the system shall
announce "There are no active alarms at this
time", then say "good by" and hang up.
Optionally, the Main Menu of the system may be accessed
from any telephone that has touch tone capability. In the
occasion where touch tone telephones are not available
the contractor shall furnish the customer a specified
number of tone encoders that will operate the system on a
pulse or rotary type telephone set or network.
- The
system shall have a telephone handset or keypad and
microphone furnished with the system. The keypad and
microphone of the system shall be capable of being
removed entirely to prevent any unauthorized change of
data into the system. In addition the keypad and
microphone (or telephone handset) shall be capable of
being temporarily relocated to a quieter location up to
100 feet from the main system to allow for programming in
noisy environments. This keypad and microphone shall be
capable of dialing out on the telephone network as an
ordinary telephone and shall be capable of interfacing
directly with the system and shall be the device that
inputs both telephone numbers and voice messages data
into the system. The operation of the telephone handset
shall be controlled by a phone/system switch that is
accessible to the operator.
- The
dialer shall have a valid FCC registration number per
Part 68, and shall comply with the any new or existing
FCC requirements at the time of sale.
- Dialers
with patented or patent pending features shall not use
these features as means of limiting competitive bidding
on this contract.
- Due to
space constraints the system enclosure as described
herein shall be of sufficient size to accommodate each
main or auxiliary feature of the system without
additional space requirements above the physical
dimensions of the system enclosure. The standard size
polycarbonate system shall be no larger that 4.69 x 8.15
x 3.58 (h l w inches)
- The
system as described here shall be designed for minimum
down time and ease of component replacement in the
future, should such replacement be necessary. Thus, all
major and minor integrated circuits of the system to
include the microprocessor chip shall be installed in
gold plated IC sockets of the appropriate type. Excluded
from this requirement are relay packs, resistors,
capacitors, crystals, diodes, discrete components and
opto couplers. This provision will allow the customer to
easily remove and replace components as his experience
level will allow. Systems that solder IC directly onto
the boards will be considered unacceptable for this
application because the boards of the system would have
to be removed from service and returned to the factory
for IC changes.
- Systems
that are made in the USA are preferred. All contacts,
fingers, and plug in devices to include edge card
connectors, boards, and ribbon cable connectors shall be
gold plated to provide the best protection against
corrosion and environmental contaminants.
OPTIONS
AVAILABLE
The system
shall be capable of being furnished with an optional heating and
ventilation system that shall be controlled by a customer
adjusted thermostat that shall provide the necessary heat to
allow the system to function in a hostile environment or standard
ambient conditions. The circulating fan system shall be
controlled by a switch that is customer accessible and will allow
the customer to select the ventilation requirements as the local
conditions dictate. When all of these optional features are
selected the size of the enclosure shall not exceed 12 x 12 x 6
(inches).
As an option
the system shall be capable of being installed in a stainless
steel NEMA 4 or 4x enclosure with a hinged door that shall be
water tight. This optional enclosure shall be utilized in hostile
environments. When specified as a hostile environment subject to
vandalism, a solid stainless steel door may be required and in
such cases the entire system shall be enclosed within the
standard enclosure not to exceed dimensions of 12 x 12 x 6
inches. Also, included in the hostile environment enclosure shall
be a standard touch tone telephone capable of making outgoing
local and long distance calls. Enclosure dimensions listed above
are maximum permitted for this design and specification. The
optional stainless steel enclosure shall be furnished with a key
lock that shall lock the system enclosure door at times when the
operator is not on site. The system shall be capable of being
enclosed in a water resistant cabinet with or without an optional
see through door. The see thru door would provide visual access
to the system without the necessity of opening an enclosure door.
Updated
3/98
Back to SD-8
Manual Index