FEATURE |
H&R ELECTRONICS SD-8 |
MICROTEL 500 |
| NUMBER OF TELEPHONE NUMBERS CAPABLE OF DIALING | 8 | 64 |
| NUMBER OF MONITORED CHANNELS | 8 | 8 |
| TYPE OF VOICE MESSAGE | DIGITIZED | DIGITIZED |
| SOURCE OF VOCABULARY | FACTORY INSTALL, OR USER INSTALLED | USER INSTALLED |
| ACKNOWLEDGMENT FEATURE | YES | YES |
| TIME DELAY AFTER ACKNOWLEDGE TO ALLOW FOR CALLED PARTY TO RESPOND TO ALARM. | YES,TIME SET FROM 1 MINUTE TO 99 MINUTES | YES TIME NOT KNOWN |
| TELEPHONE LINE UTILIZED | STANDARD VOICE GRADE | STANDARD VOICE GRADE |
| REMOTE ACCESS BY TELEPHONE | CHANGE TIME, MESSAGE OR GET STATUS, "BUY" ADDITIONAL TIME IF REQUIRED FOR FAILSAFE DELAY. IN ADDITION TO REMOTE PROGRAMMING . | STATUS, REMOTE PROGRAMMING |
| VOICE PROMPTS TO AID IN PROGRAMMING | YES | UNKNOWN |
| TYPE OF VOCABULARY | UNLIMITED WORDS AND PHRASES | ANY WORD/PHRASE |
| TOTAL TIME OF VOCABULARY | FOR ALARM DESCRIPTIONS 90 SECONDS FOR VOICE PROMPTS 90 SECONDS | TOTAL SPEECH 256 SEC |
| STORAGE OF VOICE MESSAGE | PERMANENT STORAGE REQUIRES NO BATTERY TO HOLD VOICE 100 YEAR RETENTION OF VOICE | 10 YRS RETENTION PROVIDED BATTERY POWER APPLIED |
| EFFECT OF NO POWER ON VOICE | NO EFFECT, WILL STILL BE NORMAL | WILL DEGRADE AND BE SCRAMBLED |
| DELAYS AVAILABLE TO CUSTOMER | 0 TO 99 SECONDS AND 0 99 MINUTES | NOT STATED |
| OPERATION IF THE SYSTEM IF ACKNOWLEDGED | THE SYSTEM WILL REMAIN IN A QUIESCENT STATE UNTIL THE FAILSAFE TIME DELAY HAS EXPIRE. NEW ALARMS HAVE NO HIGHER PRIORITY | NEW ALARM WILL CAUSE SYSTEM TO RE-DIAL ALARM CONDITION |
| WARRANTY | TWO YEARS | TWO YEARS |
| STANDARD SYSTEM | MONITORS EIGHT CHANNELS | REQUIRES I/O CARD FOR EACH ALARM |
| TYPE OF ALARM CONTACTS | EACH UNIT MAY HAVE N/O OR N/C | THIS IS CONFIGURED BY INSERTING CARDS FOR EACH CHANNEL |
| NUMBER OF BOARDS INVOLVED IN 8 ALARM CONDITIONS | TWO | 9 TOTAL ONE MOTHER, 8 I/O |
| ADDITIONAL EQUIPMENT REQUIRED TO TRANSMIT TO COMPUTER SYSTEM | NOT AVAILABLE | AVAILABLE AT ADDITIONS COST |
| PROGRAMMABLE RING COUNT BEFORE HANG UP | USER SELECTED 1 TO 99 | 1 TO 20 |
| PROGRAMMABLE CALL INTERVAL | SELECTED BY CUSTOMER AT THE MAIN MENU FROM 0 , 1,2,5 OR ANY 4 OTHER SEQUENCE IF IDENTIFIED PRIOR TO SHIPMENT | 1 TO 999 MINUTES |
| ACCESS CODE REQUIRE TO ACCESS SYSTEM REMOTELY | 4 DIGIT CODE SELECTED BY CUSTOMER | 4 DIGITS BY CUSTOMER |
| ACCESS OF STATUS INFORMATION | FREE TO ALL WITHOUT CODE | REQUIRES 4 DIGIT CODE |
| ACCESS OF PROGRAMMING SYSTEM | REMOTELY WITH CODE | REMOTELY WITH CODE |
| NUMBER OF MESSAGE REPETITIONS | MESSAGE COMPOSED AT THE TIME CUSTOMER
RECORDS EACH OF THE 8 ALARM MESSAGES. TOTAL TIME SET
ASIDE FOR ALARM MESSAGES OF ANY LENGTH NOT TO EXCEED 90
SECOND. CALLED PARTY MAY ENTER 3 DIGIT CODE TO REPEAT THE ENTIRE MESSAGE AS EACH TELEPHONE CALL CONDITION MAY DICTATE |
1 - 20 REPETITIONS (FIXED) |
| ABILITY TO RESPOND TO BUSY OR ANSWER ON THE TELEPHONE NETWORK | YES | YES |
| METHOD OF DIAL OUT | TOUCH TONE | TONE, OR PULSE(OLD STYLE OF DIALING) |
| PROGRAMMABLE FEATURES | SPEECH, TELEPHONE NUMBERS, TIME DELAYS TYPE OF CONTACT CLOSURE CAPABLE OF PROGRAMMING ALL VARIABLES FEATURES EXCEPT TIME WINDOW FOR PAGER WHICH IS SELECTED VIA TELEPHONE CONTACT BY FACTORY AUTHORIZED PERSONNEL | SPEECH, TEL NO.'S AND OTHER UNSPECIFIED FUNCTIONS |
| TYPE ENCLOSURE | FIBERGLASS NEMA 1 WITH THE OPTIONS FOR STAINLESS STEEL, NEMA 4, OR OTHER ENCLOSURE NOT LIMITED TO ANY SPECIAL ENCLOSURE | NEMA 4X FIBERGLASS |
| CIRCUIT BOARD THEORY | TWO STACKED BOARDS(8 CHANNELS) | 8 DIFFERENT BOARDS, PLUS MOTHER BOARD |
| TYPE OF LIGHTNING ARRESTOR ON TRIP CIRCUITS | OPTO ISOLATORS, WITH POWER SUPPLY W/ CROWBAR TYPE FEATURE | GAS TUBE /ZENIER |
| TYPE OF LIGHTING PROTECTION ON TEL LINES | SIDACTOR CAPABLE OF DISSIPATION 600
VOLTS OTHER LIGHTING PROTECTION IS AVAILABLE. THE 9 VOLT TRANSFORMER OFFER SUPERB PROTECTION FROM SPIKES AND TRANSIENTS |
GAS TUBE /ZENIER |
| BATTERY BACK UP | 24 HOURS | 24 HOURS |
| METHOD OF ENTERING DATA INTO SYSTEM | STANDARD TELEPHONE HANDSET INCLUDED IN SYSTEM | KEYPAD ON UNIT |
| VERIFICATION OF ENTERED DATA | AVAILABLE VIA LCD DISPLAY ON THE ENTRY HANDSET | LCD DISPLAY |
| LCD DISPLAY | SINGLE LINE LCD FOR TELEPHONE ALL DIGITAL INPUTS | 40 CHARACTER LCD |
| STORAGE OF DATA INCLUDING TELEPHONE NUMBERS | NON VOLATILE MEMORY | NON VOLATILE MEMORY |
| INTERNAL DIAGNOSTICS | LED DISPLAY OF ALL OPERATING VOLTAGES ON THE SYSTEM | NUMBER OF CALLS PLACED, RECV, AND POWER FAILS |
| ABILITY TO DETECT VALID TEL LINE STATUS | VIA LED DISPLAY | YES |
| LCD DISPLAY OF HELP IN PROGRAMMING | YES NUMBER ENTERED VIA THE HANDSET | YES |
| NUMBER OF O & M MANUALS FURNISHED | 3 ADDITIONAL AS REQ'D @ $10 EACH | 3 |
| ABILITY TO DIAL A PAGER AND ENTER THE STATION LOCATION CODE | (3 DIGITS) AND THE REMAINING DIGITS 1-8 DEFINING THE VARIOUS ALARM CHANNEL WHICH HAVE BEEN ACTIVATED AND TIME OUT PER TIME SET BY CUSTOMER | NOT STATED PROBABLY NOT AVAILABLE NO A/C FAIL IN ADDITION TO 8 CHANNELS |
| ABILITY TO DIAL A PAGER AND ENTER THE A/C POWER FAIL CODE | THE NUMBER 9 DIGIT IS TRANSMITTED WHEN THE CUSTOMER SELECTS TO MONITOR THE INTERNAL A/C POWER FAIL | NOT STATED PROBABLY NOT AVAILABLE NO A/C FAIL IN ADDITION TO 8 CHANNELS |
FEATURES FOUND IN THE SD-8 BUT NOT THE MICROTEL 500
SELECTABLE TELEPHONE DIALING SEQUENCE WHICH WILL ALLOW FOR THE TEMPORARY DELETION OF ONE OR MORE TELEPHONE NUMBERS WITHOUT REMOVING THE NUMBER FROM THE DIRECTORY.
INDIVIDUAL BY PASS SWITCHES FOR EACH ALARM WHICH WILL ALLOW ANY OR ALL CHANNELS TO BE SELECTIVELY BYPASSED IN THE EVENT OF A MALFUNCTION OF AN INDIVIDUAL CHANNEL
24 PRE-RECORDED PROMPTS WHICH CAN BE RE-PROGRAMMED BY THE CUSTOMER IF REQUIRED.
THE ABILITY TO SELECT AN PLAY EITHER THE ENTIRE MESSAGE GROUP OF ALARMS OR THE ENTIRE MESSAGE GROUP OF PROMPTS
FACTORY DEFAULT TEST VALUES SELECTABLE AT MAIN MENU TO FACILITATE THE PROGRAMMING AND SETUP OF THE SD-8
THE ELECTION OF N/O OR N/C CONTACT TYPE BY CUSTOMER W/ HANDSET. DEFAULT SETTING ARE N/O.
MONITOR THE PRESENCE OF A/C POWER AT THE TRANSFORMER WHICH WOULD GIVE A GENERAL POWER FAIL ALARM IF SO SELECTED BY THE CUSTOMER. NOT RECOMMENDED TO MONITOR BROWN-OUT OR PHASE LOSS. THIS REQUIRES A PHASE MONITOR.
TIME DELAY SELECTED BY CUSTOMER FROM 1 - 99 MINUTES FOR A/C FAILURE.
THE ABILITY TO DIAL A TONE PAGER AND INSERT TONE INFORMATION DESCRIBING THE STATION LOCATION W/ A 3 DIGIT CODE AND ALL OTHER MONITORED ALARMS INCLUDING POWER FAILURE (INTERNAL)
THE ABILITY TO SELECT THE 3 DIGIT CODE IDENTIFIER USED IN THE PAGER CODE TO IDENTIFY THE CALLING UNIT. ALLOWS FOR 1 TO 999 STATION CODES.
LED LIGHT WHICH WILL DISPLAY IF THE SYSTEM IS IN AN ACKNOWLEDGE MODE.
LED LIGHT WHICH WILL INDICATE WHEN THE SYSTEM IS OFF HOOK AND DIALING.
A ON SITE SPEAKER WHICH WILL ALLOW THE CUSTOMER TO HEAR THE TOUCH TONE DIALING PATTERN AND ALL OF THE VOICE PROMPTS AND MESSAGES.
LED LIGHT WHICH WILL IDENTIFY EACH OF THE 8 CHANNELS WHICH ARE IN THE BYPASS MODE.
8 LED LIGHTS WHICH WILL IDENTIFY WHICH ALARM CHANNELS ARE CLOSED IN ALARM.
8 LED LIGHTS WHICH WILL IDENTIFY WHICH ALARMS CHANNELS HAVE TIMED OUT AND ARE VALID ALARM CONDITIONS.
THE ABILITY TO VISUALLY IDENTIFY WHEN AN ALARM CONDITION HAS OCCURRED AND TIMED OUT AND IS NOT IN ALARM AT THE PRESENT TIME.
REMOTELY MOUNTED RESET SWITCH WHICH CAN BE ACCESSED WITHOUT OPENING THE UNIT.
VISUAL DISPLAY OF 36 LED's WHICH DEFINE VARIOUS STATUS CONDITIONS OF THE SD-8
THE ABILITY TO RESET THE FAILSAFE TIMER TO GAIN ADDITIONAL TIME SHOULD THE RESPONDING PERSON HAVE DIFFICULTY IN GETTING TO THE STATION TO RESPOND TO THE ALARM. THIS IS DONE VIA TELEPHONE AND A 4 DIGIT SECURITY CODE.
POSITIVE CONFIRMATION THAT THE DIALER HAS RECEIVED THE ACKNOWLEDGE TONE BY THE PHRASE ACKNOWLEDGMENT RECOGNIZED@ WHICH IS BROADCAST UPON RECEIPT OF VALID TONE ACKNOWLEDGMENT.
THE OPTION OF ORDERING THE SYSTEM WITH THE ABILITY TO HALT THE SYSTEM FROM A TELEPHONE COMMAND, THIS MUST BE IDENTIFIED PRIOR TO DELIVERY. NOT STANDARD
THE ABILITY TO REMOTELY SET THE FAILSAFE TIMER INTO A COUNT DOWN MODE VIA TELEPHONE W/ PROPER CODE AUTHORITY.
SPECIAL DELAY BEFORE DIALING DELAYS ARE AVAILABLE FOR SPECIFIC APPLICATIONS.
ACTUAL SIZE OF THE UNIT WITH BATTERY IS APPROXIMATELY 7.5 X 4 X 4 AND WEIGH LESS THAN 6 POUNDS.
COMES COMPLETE WITH BATTERY, TRANSFORMER, SCREWDRIVER AND 2 TYPES OF TELEPHONE CORDS ONE WITH A MODULAR JACK AND THE OTHER WITH SPADE LUGS CONNECTIONS FOR UNDER SCREW MOUNTING.
THE UNIT CAN BE CONFIGURED TO WORK IN CONJUNCTION WITH THE ADCOR CELLULAR TYPE COMMUNICATOR WHICH WOULD ALLOW THE SYSTEM TO WORK IN AREAS WHERE CONVENTIONAL TELEPHONE LINES ARE NOT AVAILABLE. ADVISED PRIOR TO ORDERING.
PROVISIONS FOR REPEATING THE VOICE MESSAGE IS ALLOWED TO THE CALLED PARTY BY THE ENTRY OF 3 DIGITS.
THE ABILITY VIA TELEPHONE TO REMOTELY RESET THE UNIT THIS IS THE SAME AS DEPRESSING THE LOCAL RESET BUTTON.
OPTIONAL FEATURES INCLUDED THE ABILITY TO LEAVE A SCRATCH PAD MESSAGE FOR OTHER PERSONS TO RECEIVE UPON CALL IN AND REQUESTING THIS DATA.
CUSTOM PROGRAMMING OF THE MICROPROCESSOR TO GIVE SPECIAL CONSIDERATION TO UNIQUE CONDITIONS OF A SPECIFIC CUSTOMER.
THE ABILITY TO CUSTOM MOUNT OR PANEL MOUNT THE SD-8 UNIT IN A VERY SMALL SPACE IN AN EXISTING OR PROPOSED PANEL OF OTHERS.
THE VOLTAGE INTO THE SYSTEM IS LOW VOLTAGE DC CURRENT (9 VOLTS D/C).
DIRECT SHORTS ON THE ALARM CHANNELS WILL NOT DESTROY THE SYSTEM, PROTECTED BY A CROW BAR TYPE POWER SUPPLY.
OTHER PROPOSED FUTURE OPTIONS INCLUDE THE ABILITY TO ADD A LCD DISPLAY, AND ADDITION ALARM CONTACTS.
CURRENT STATE OF THE ART VOICE STORAGE IN DIGITIZED FORMAT WHICH CAN BE SHIPPED FROM THE FACTORY AND REMAIN WITH OUT POWER FOR YEARS AND STILL RETAIN THE ABILITY TO SPEAK.